The Rectiverter Scalable System 120 kW provides backed-up power for 400 VAC three-phase or 230 VAC single-phase loads together with 48 VDC for DC loads and battery charging. Its maximum capacity of 108 kW is shared dynamically, supplying up to 90 kVA / 72 kW of AC and up to 72 kW of DC through built-in AC and DC distribution. With the optional B input (dual AC input), a traditional ATS is no longer needed.
Key Features
- 400 VAC three-phase (Y) input and output
- 48 VDC input/output
- Up to 90 kVA / 72 kW AC and up to 72 kW DC
- AC distribution with up to 30 breakers; DC distribution option
- Optional A+B dual AC input replaces a traditional ATS
- Up to 4 battery strings with LVBD
- 150% overload for 15 s, 600% quick-trip for 20 ms
- Hot-pluggable, Smartpack2 controller, operates in parallel with Flatpack2 rectifiers
Technical Specifications
| Input | |
|---|---|
| Current (maximum) | 1920 ADC |
| Voltage AC (operating range) | 320 – 475 VAC |
| Voltage DC (operating range) | 40 – 58 VDC |
| Max Input AC Voltage | 475 VAC |
| Max Input DC Voltage | 58 VDC |
| Mains Configuration | 230/400 VAC 3 phase (Y) |
| AC Output | |
| Voltage (adjustable) | 346 – 415 VAC |
| Max Output AC Voltage | 415 VAC |
| Max Power | 90 kVA / 72 kW |
| DC Output | |
| Voltage (adjustable range) | 43 – 58 VDC |
| Current (maximum) | 1500 ADC |
| Max Voltage | 58 VDC |
| Max Power | 72 kW |
| Battery Distribution | |
| Breaker Positions Up to | 4 |
| Breaker Rating Up to | 1600 A |
| LVBD | Yes |
| DC Load Distribution | |
| Breaker Positions Up to | 30 |
| Breaker Rating Up to | 120 A |
| LVLD | No |
| AC Load Distribution | |
| Number of Breakers | 30 |
| Breaker Rating Up to | 63 A |
| Others | |
| Cooling | Single fan |
| Operating Temperature | −40 to 55°C |
| Storage Temperature | −40 to 85°C |
| Dimensions | |
| Dimensions (W x H x D) | 1200 x 2000 x 600 mm [47.4 x 78.8 x 23.7 inch] |
| Mounting Dimensions | Width 19 inch / Height 44U / Depth 600 mm |
| Weight | 500 kg |
| Design Standards | |
| Ingress Protection (IP) | 20 |
Specifications from Delta Electronics (Eltek) and subject to change without notice. Contact KPS for the latest datasheet.
Applications
Large telecom hubs, data rooms and industrial facilities that need scalable AC UPS and 48 VDC power from one battery plant.
Related Eltek Products
- Rectiverter Scalable System 18-72 kVA – 36, 54 or 72 kVA plus 57.6 kW DC
- Rectiverter Scalable System 18-54 kVA – modular AC UPS for 48, 110 or 220 VDC
- MiniCPS 65 kW Power System – combined AC UPS and 48 VDC cabinet
Browse the full Rectiverter system range or see all Delta Eltek DC power systems in Egypt.
Buy Rectiverter Scalable System 120 kW in Egypt